Wireless Barriers Coding Rules |
2021.01.07 |
|
1. After the code is successfully paired, block barriers a while and move the block, and block after the alarm period has passed.
Trigger according to 6S or 120S alarm cycle. Each block interval needs to be 6 seconds or 120 seconds, and the specific alarm interval is determined by the internal dial code.
2. After successful code matching, continue to block the wireless barriers.
The alarm period will gradually lengthen, and will be lengthened according to the doubling interval. It will be 6S, 12S, 24S, 48S...... Until 2h, it is still covered at this time, and the alarm code will be sent every two hours. When the covering is removed, the alarm cycle will return to normal.
3. Low-power code sending logic.
When the battery is below 2.9V, a low code will be sent. The code sending logic is the same as that of the wireless barriers continuously shielding and sending the alarm code. According to 6S, 12S, 24S, 48S... until 2h, the low code will be issued every two hours. Until the battery is replaced or the battery is dead.
|
|
|
|
|